Standard Dimensions

SERIES 2500/2500-1 | ||||||||
---|---|---|---|---|---|---|---|---|
Valve Size | 2" | 2-1/2" | 3" | 4" | 6" | 8" | 10" | 12" |
A | 8.44 | N/A | 11.84 | 13.91 | 17.12 | 20.47 | 24.06 | 27.59 |
B | 9.36 | N/A | N/A | N/A | N/A | N/A | N/A | N/A |
End to End | 7.75 | N/A | 8.62 | 10 | 10.5 | 11.5 | 12.5 | 13.5 |
Lay Length | 2.75 | N/A | 3.62 | 5 | 5.5 | 6.5 | 7.5 | 8.5 |
Handwheel Dia. | 7 | N/A | 8 | 10 | 12 | 14 | 15.5 | 15.5 |
NOTES
- 3" through 12" valves meet or exceed requirements of ANSI/AWWA C515.
- 2-1/2" through 12" valves may be ordered in configurations that are UL Listed and FM Approved.
- 2" through 12" valves have 250 psig AWWA rated working pressure.
- 2-1/2" through 12" valves have 250 psig UL and FM rated working pressure.
- Fusion-bonded epoxy coating meets or exceeds requirements of ASME/AWWA C550.
- Mechanical joint ends are in accordance with ANSI/AWWA C111/A21.11.
- MAINTENANCE: Each valve should be operated through a full cycle and returned to its normal position. This should be done on a time schedule that is designed to prevent a buildup of tuberculation or other deposits that could render the valve inoperable or prevent a tight shutoff. It is recommended that this be done once a year.
- Open direction is specified by the customer.