Standard Dimensions
4"-12"
Size | 4" | 6" | 8" | 10" | 12" |
---|---|---|---|---|---|
A | 13.91 | 17.12 | 20.47 | 24.06 | 27.59 |
B + .000/- .031 | 4.984 | 6.984 | 8.984 | 10.984 | 12.984 |
C +/- .016" | 0.188 | 0.25 | 0.25 | 0.25 | 0.25 |
D (Flange End) TF (Class 125) |
4.5 | 5.25 | 5.75 | 6.5 | 7 |
E (MJ End) TM | 5 | 5.25 | 6.62 | 7.12 | 7.38 |
F | 2.5 | 2.5 | 2.5 | 2.5 | 2.5 |
G Waterway Diameter | 4.25 | 6.25 | 8.25 | 10.25 | 12.25 |
Tap Size | 3/8 NPT | 3/8 NPT | 3/8 NPT | 3/8 NPT | 3/8 NPT |
Maximum Cutter Diameter |
4 | 6 | 8 | 10 | 12 |
14"–24"
Size | 14" | 16" | 18" | 20" | 24" |
---|---|---|---|---|---|
A | 33.25 | 36.75 | 39.63 | 43.25 | 51.25 |
B | 14.94 | 16.94 | 18.94 | 20.94 | 24.94 |
C | 0.25 | 0.25 | 0.25 | 0.25 | 0.25 |
D | 7.5 | 8 | 8.5 | 9 | 10 |
E | 10.25 | 10.44 | 11.44 | 11.75 | 12.75 |
F | 3.5 | 3.5 | 3.5 | 3.5 | 3.5 |
G | 14.19 | 16.19 | 18.13 | 20.13 | 24.13 |
H | 7.63 | 7.56 | 8.43 | 8.63 | 9 |
T | 18.75 | 21.25 | 22.75 | 25 | 29.5 |
U | 18.75 | 21 | 23.25 | 25.5 | 30 |
X | 12-1.13 | 16-1.13 | 16-1.25 | 20-1.125 | 20-1.38 |
Y | 10-.88 | 12-.88 | 12-.88 | 14-.88 | 16-.88 |
Tap Size | 3/8 NPT | 3/8 NPT | 3/8 NPT | 3/8 NPT | 3/8 NPT |
Maximum Cutter Diameter |
14 | 16 | 18 | 20 | 24 |
Notes
- 4"–36" valves meet or exceed requirements of ANSI/AWWA C515.
- 4"–16" valves may be ordered in configurations that are Listed by Underwriters Laboratories Inc. (UL) and Approved by FM Global.
- 18"–24" valves may be ordered in configurations that are UL Listed.
- 4"–48" valves have 250 psig ANSI/AWWA rated working pressure.
- 4"–12" valves in UL Listed and FM Approved configurations have 250 psig UL FM rated working pressure.
- 14"–16" valves in UL Listed and FM Approved configurations have 200 psig UL Listed and FM Approved rated working pressures.
- 18"–24" valves in UL Listed configurations have 175 psig UL rated working pressure.
- Fusion-bonded epoxy coating meets or exceeds requirements of ANSI/AWWA C550.
- Mechanical joint ends are in accordance with ANSI/AWWA C153/A21.53 and MSS SP-113.
- Bolt patterns of flanged ends are in accordance with ANSI/AWWA C110/A21.10. (ASME B16.1 Class 125).
- Raised alignment ring dimensions of flanged ends on tapping valves are in accordance with MSS SP-60.
- Tapping valves are supplied with flanged-end hardware, including bolts, nuts, ring-type gasket and flange protection kit. The flange-end bolting is furnished in the same material as specified for the valve body bolting.
- 4"–48" valves are Certified to NSF/ANSI Standard 61.