Laying Lengths

2 1 3 5 2 Wall Pipe Laying Lengths Print
Size
(in.)
Minimum Dimensions in inches
Flg-T/C-Flg Flg-T/C-PE PE-T/C-PE MJ-T/C-MJ (Fab1) MJ-T/C-PE MJ-T/C-Flg Fst-T/C-PE Fst-T/C-Flg
O.A./L.L. O.A./L.L. O.A./L.L. O.A. L.L. O.A. L.L. O.A. L.L. O.A. L.L.1 O.A. L.L.1
4 8 8 8 10 4 5/8 8 5 1/2 8 5 1/2 8 4 11/16 8 4 5/8
6 8 8 8 10 4 5/8 8 5 1/2 8 5 1/2 8 4 5/8 8 4 5/8
8 8 8 8 10 4 5/8 8 5 1/2 8 5 1/2 4 1/4 8 4 1/4 4 1/4
10 8 8 8 10 4 5/8 8 5 1/2 10 7 1/2 8 4 1/4 7 1/4 3 1/2
12 8 8 8 10 4 5/8 8 5 1/2 10 7 1/2 8 4 1/4 7 1/4 3 1/2
14 8 1/2 8 8 12 4 1/2 8 4 1/2 11 7 1/2 8 2 3/4 9 3/4 4 1/2
16 8 1/2 8 8 12 4 1/2 8 4 1/2 11 1/2 8 8 2 3/4 9 3/4 4 1/2
18 8 1/2 8 8 12 4 1/2 8 4 1/2 12 8 1/2 8 1 1/2 10 4 1/2
20 8 1/2 8 8 12 4 1/2 8 4 1/2 12 8 1/2 8 1 1/2 10 4 1/2
24 9 1/2 8 8 12 4 1/2 8 4 1/2 12 8 1/2 8 1 1/2 10 4 1/2
30 12 10 1/2 8 - - - - - - 8 1 1/2 12 5 1/2
36 14 11 1/2 8 - - - - - - 8 1 1/2 12 5 1/2
42 16 12 8 - - - - - - 8 1/2 1 14 6 1/2
48 16 12 8 - - - - - - 9 1 15 7
54 18 16 8 - - - - - - 9 1/2 1 16 7 1/2
60 18 16 8 - - - - - - 9 3/4 1 16 7 1/4
64 18 16 8 - - - - - - 10 1 16 7
1.) Laying lengths are rounded to the nearest 1/4".

Maximum laying length of below wall pipe is 19’-6" (except 19’-0" for 64"), except for MJ–T/C–PE or Fst–T/C–PE, which may be furnished in full 20-ft nominal length.

4"-16" Flange–T/C–Flange and Flange–T/C–PE pipe may also be furnished up to 20’-0" length. Contact AMERICAN if longer lengths are required. All intermediate lengths can be furnished.

Thrust Collars may not be located in exact center of all minimum-length pieces shown above.

Flanges and mechanical joint bells of minimum-length pieces should normally be specified by the purchaser as “tapped for studs” to enable assembly of joints flush with the wall face.

Wall pipe lengths shorter than those shown here can be furnished in some sizes by special fabrication. Contact AMERICAN for details.

Overall lengths are subject to manufacturing tolerances. If maximum overall length is critical, such as for installation of an item inside steel forms, this must be specified by the purchaser on the order.

Correctly installed flanged wall pipe will normally have the bolt holes straddling the horizontal and vertical centerlines. Checking with a spirit level or plumb line prior to pouring the walls is recommended.

Wall pipe with MJ threaded–on bells (MJ Fab), Flex–Ring, and Lok–Ring bells can also be furnished. Contact AMERICAN for dimensions not shown above.

Minimum–length pipes with plain ends (PE) in many cases do not allow enough room between PE and collar to assemble joints. Contact AMERICAN for PE joint assembly needs, normally requiring longer pipes.